In floor fitting, less cover and
flange. Hubbell introduces a multiple service fire rated poke
through fitting that combines four insulated 15 ampere, 125V
receptacles with four category 5 jacks to be installed in a 3" cored
hole. This additional service capacity provides the maximum in
flexibility if requirements change. Four power receptacles with
two-circuit wiring capability and up to four category 5 modular
jacks mount flush to the cover for an unobtrusive appearance. Covers
and flanges are available in gray, black, ivory and brass colors.
These units are UL Listed for floors with a 1-4 hour fire rating.
|
| Hubbell Wiring Device-Kellems Product
Specifications |
| Poke-Through Style |
|
| Type |
4 Outlet Flush |
| Item |
Through Floor Fitting Only-1 or
2 Circuit |
| Core Hole Size |
3" |
| Flush Service Type |
4 outlet with up to 4 flush
category 5 jacks |
| Fire Rating |
For use in 1, 1 1/2, 2, 3, or 4
hour rated unprotected reinforced concrete floors or in 1, 2, or 3
hour rated floors employing steel floor units and concrete topping
(D900 Series design). |
| Floor Thickness Range |
2 1/4" (over metal deck) to 7"
(57.2mm to 177.8mm). |
| UL Installation Spacing |
Minimum of 2 feet on centers
and not more than one unit per each 65 sq. ft. of floor area in each
span. |
| Cored Hole |
3" (76.2mm) diameter. |
| Receptacle |
NEMA 5-15R; 15A 125V. |
| Power Conduit Tubes
Material |
3/4" EMT |
| Low Voltage Conduit Tubes
Material |
1/2" EMT (two). |
| Outlet Box UL Listing |
E31999 |
| Fire Resistance UL
Listing |
R8429 |
| Style |
Flush |
| Features/Benefits |
| Features |
Benefits |
| • Four insulated 15A/125V receptacles. |
• Perfect solution for single circuit or two-circuit
applications. |
| • Up to four flush mounted category 5 jacks. |
• Reliable voice and data services. |
| • 1, 1 ½, 2, 3, or 4 hour fire rating. |
• Superior fire barrier provides highest level of
protection in a 3" cored hole. |
| • All brass appearance available. |
• Attractive economical alternative to solid brass. |
| • Receptacle housing mounts to fitting. |
• Cover and flange may be installed or removed without
removing receptacle housing. |
| • Low voltage conduit entrances. |
• Convenient cabling protection when
needed. | |
|